Hanco Flux-Power Transformer Switching Device Ratings

Model KVA:

Primary Voltage:

Safety Switch Size (Amps):

Circuit Breaker or Time Delay Fuse (Amps):

Wire Size Type R, T:

Contactor Size:

Full Load Amps:

FL50-4  15 KVA

220

200

150

2

4

68

440

100

80

6

3

34

550

100

60

8

3

27

FL60-4  20 KVA

220

200

200

0

5

91

440

200

110

6

4

45

550

200

80

6

3

36

FL70-4F  30 KVA

220

400

300

3/0

5

136

440

200

150

2

4

68

550

200

125

4

4

55

FL80-4  40 KVA

220

400

400

4/0

5

182

440

200

200

0

5

91

550

200

150

2

4

73

Fuse Size = 2.25 x Full Load Amps

© 2008 The Hannon Company. All Rights Reserved. 

< Back to Homepage > / < Back to Screen Heating >